15
E-Mail Setup
[Setup] / E-Mail
Note: This is only needed if you have an Ethernet connection and want the system to send e-mail messages.
Parameter Parameter Value
Description
Value
“From” Address
your_from@
address.com
Enter e-mail address of sender (console) abc#
(40 Characters Maximum)
SMTP Host
Your SMTP host
address
Enter I.P. address of SMTP host
abc#
(40 Characters Maximum)
SMTP Port 25
Port address of SMTP
0-65535
Enable Authentication No
Data authentication (if required)
Yes / No
Maximum Queue Size 20
Maximum size of queue in Megabytes
0-200
Retry Timeout 3600
Time, in seconds, that the console will wait before
attempting to resend the message.
86400 max
Watchdog Timeout 30
Time, in seconds, that the console self-monitoring
program waits when it expects an error due to
software or power quality problems.
0-300
Enable Debugging No Keeps record of communication attempts Yes / No
System Sentinel AnyWare
[Setup] / System Sentinel AnyWare
Note: This section of Set-up is only required if the console is going to transmit data to SSA. It will require the assistance
of the SSA Administrator to set up.
Setup would require:
1. Contact an SSA Administrator.
2. The console must be connected through an Ethernet connection.
3. The SSA Administrator must create a site on SSA.
4. On the SSA Site / Setup page there is an EPS option.
5. Click on EPS.
6. You will be prompted with a note “Program EPS for this site?”
7. Click yes, and the program will automatically enter the values in the table below.
Parameter Parameter Value
Description
Value
IP Address
IP address of SSA server abc#
(40 Characters Maximum)
Port 80
The port that the SSA server uses
#
Path
/ssa/_data/ssa_
webdata.dll
This is the Web Data URL located on the SSA
server but without the http:// and the domain
name.
abc#
(40 Characters Maximum)
Priority Highest
Sets communication priority. Leave this at High or
Highest.
Highest, High, Normal, Low
Database Connection SSA1
Name of Database. For most applications this is
left blank.
abc#
(40 Characters Maximum)
Database User Name SSAADMIN
Name used to access the database abc#
(40 Characters Maximum)
Database User
Password
Password of the user above to access the
database.
abc#
(40 Characters Maximum)
Site ID (0) Can leave this at 0. #