LS500 Auto Learn Line Leak DetectionInstallation & User’s Guide Franklin Fueling Systems • 3760 Marsh Rd. • Madison, WI 53718 USATel: +1 608 838
104-20mA Input ModuleTS-LSU500 Transducers use a single 4-20mA channel per product line which allows the console to monitor the pressure on each produ
11Relay ModuleThe 2A relay module contains 8 separate relays, called relay channels. The 10A relay module contains 6 relay channels. Each relay is use
12Turbine Pump Interface (TPI) ApplicationsIn systems where TPI is used, the relays are not needed for line leak or STP operation. Communication with
13Fuel Management Systems (FMS) Line Application Set-UpSetting up the lines establishes which transducer and relay is used on the specic line and all
14Line Status and Control ScreensThe status of each line channel can be viewed at any time by navigating to the Line Status or Control screens. To get
15LS500 Control ScreenStatus SectionIndicator DescriptionLine Pressure Indicates the current line pressureEnabled Green, enabled. Red, disabledNot Lea
16Pre-Operational LS500 TestingThe line stability test procedure assumes that all STP’s, pump controllers, and AC inputs have been installed, wired, c
17Learn ProcessEach line must be learned before the FMS system can continuously monitor it. Learning involves bleeding the line pressure down to zero,
185. When nished, the message Learn Completed – No Errors is displayed on-screen and the Not Learned indicator will become inactive.Note: If any er
19LS-500 ReportsLine test reports are available on demand from the console or using the web page. The reports can also be generated by using the rules
Copyright ©2008 by Franklin Fueling Systems (FFS). No part of this publication may be reproduced in any form without the prior written consent of FFS.
20LS-500 Alarms and WarningsAlarms During the Learn Process Alarm Symptom Possible Cause ResolutionFailed to pressure up STP is not turning on Ver
21Catastrophic leak Investigate for leaksIs the clamp valve down Look at the pressure gauge on the needle valve kit for operating pressureTest Result
22Test Result AlarmsTest Result Condition Possible Cause ResolutionPass Line is tightFail Actual Leak Line pressure variations are outside thresholdCh
23LS-500 Functional TestingPerform a Functional Test annually. This test will verify that the LS-500 application will detect and alarm on a leak condi
©2012 FFS 000-2145 Rev.E
3ContentsNotice...2Import
4Important Safety MessagesINCON equipment is designed to be installed in association with volatile hydrocarbon liquids such as gasoline and diesel fue
5OverviewThe TS-LS500 is a continuous product line leak detection system that monitors the primary pipe. This product is an available option of Frankl
6Figure 2: TS-LSU500 Dimensions6.25"(159 mm)5.13"(130 mm)2" NPT3/4" NPT2-3/8" (70mm) across atsDenitions and AcronymsAIM
7Intrinsically Safe LS500 InstallationNote: The Intrinsically Safe 4-20mA Input Module has a BLUE face. WarningLockout and tag circuit breakers, and
8Explosion Proof LS500E InstallationNote: The Explosion Proof 4-20mA Input Module has a RED face. WarningLockout and tag circuit breakers, and discon
9LS-500 Setup (Console Programming)The following instructions are a guide to programming the LS-500 only. The administrator password will be necessary