DTU (Data Transfer Unit) Setup and Programming
1. Under Setup / System Conguration/Modules Expected, set Console DTU to 1.
2. Under Setup, locate Remote DTUs. The Network ID number will be defaulted to 1.
3. Enter the number of Remote DTUs installed in Number of Units.
Note: Remote DTUs refers to the units in dispensers only.
4. For each Remote Data Transfer Unit, you must enter the unique Unit ID #. This number can be found on the label
included with each Remote DTU. Enter this number for each one.
5. Under PROBE MODULES, locate REMOTE MODULE (DTU) and enter the number of Remote Data Transfer
Units installed. Each Probe channel refers to the VFM channel on the Remote DTU. The maximum number of
channels per REMOTE MODULE is 12.
6. For each Channel, enter a name for the Vapor Flow Meter connected to the channel.
7. Select TS-VFM for the type.
8. If more than 12 channels are necessary, program REMOTE MODULE (DTU). If there are no internal Probe
Modules congured then the rst Remote Module will be 1. Follow Steps 5 through 7 to complete all DTUs in the
system.