Select the DIM Diagnostic in the Diagnostics section of the
Main Menu (Figure 4).
Figure 4: Diagnostics Screen
Once selected you will be prompted to conrm your
selection (Figure 5).
Figure 5: Conrmation Screen
Select OK and you will be prompted to enter the
Administrator password. Enter the password and select the
check box Figure 6).
Figure 6: Password Screen
The system will now enter DIM Diagnostic Mode (Figure 7).
Figure 7: Diagnostic Mode
Step 2
Connect to the console via an Ethernet connection,
and reboot the system (soft boot) by choosing
tools \ reboot system.
Using a NULL modem cable connect COM Port 2 of the T5
series console to a COM port on a PC.
A
B
GND
+
-
TPI RS-485COMM2BUS EXT
FAX/MODEM
COMM 1
ETHERNET
USB
H
CURRENT LOOPRS422/232
Figure 8: T5 Console COM Port 2 Location
Open a terminal emulator program (e.g. Hyper Terminal) with
protocol setting of 57600 Baud, 8 Data Bits, No Parity, and 1
Stop Bit (Figure 9-11).
Figure 9: Terminal Program Open